
1. Freeze the operating envelope: 250 kW is not constant power over the full input range
The example uses a four-phase interleaved three-level boost, with a 350–1000 VDC input range, 1100 VDC maximum and a 1100 V calculation bus. Switching frequency is 32 kHz. Each channel is limited to 100 Arms and 62.5 kW: current-limited below 625 V and power-limited above. Four inductors share a potted 200 × 150 × 100 mm aluminum enclosure at 60 °C ambient, with a temperature-rise target below 30 K.
| Input | Document condition | Confirmation required |
|---|---|---|
| Loaded inductance | ≥80 µH at 100 A | Acceptance at load; zero-bias value for incoming inspection |
| Overload | 110% / 10 min; 120% / 1 min | Inductance, loss and temperature at 120 A |
| Ripple | Channel <20%; combined <5% | Rated or actual-current denominator; summation node |
| Coupling | Input requirement 0.2; design ≤0.05 | Independent or coupled paths, agreed with the control engineer |
| DCR and cooling | <4 mΩ at 25 °C to be confirmed; forced air | Final DCR limit, airflow and baseplate interface |
2. Four independent UU paths and inductance at 100 A
Each channel uses a 60µ FeSi powder UU core, with Ae = 1169 mm² and le approximately 194 mm. Two nine-turn coils are connected in series for 18 turns, using edgewound 2.0 × 10 mm flat copper. The four paths are independent, with a design coupling coefficient ≤0.05; combined-ripple cancellation relies on control phase shift.
Zero-bias model: L0 = N² · µ0 · µi · Ae / le ≈ 147.2 µH. At 100 A, H = N · I / le ≈ 9278 A/m. The document fits DC-bias roll-off to a material curve. The following values are calculated and exclude the temperature dependence of permeability.
| Current | Typical L (µH) | Lower-bound L (µH) |
|---|---|---|
| 0 A | 147 | 135 |
| 76 A | 125 | 111 |
| 100 A | 111 | 97 |
| 110 A | 105 | 91 |
| 120 A | 99 | 86 |
The 147 µH zero-bias value cannot replace acceptance at 100 A. For incremental inductance that falls with current, review stored energy using W = ∫ i · L(i) di instead of only substituting the operating-point inductance into ½LI². Measured room-temperature and hot L-I curves take precedence.
3. Separate channel ripple, combined ripple and phase shift
Under the article's three-level modulation assumption, the inductor voltage switches in Vbus/2 steps and ripple frequency is 2fs = 64 kHz. Verify this against the actual PWM timing. The linear approximation is ΔIpp = (Vbus/2) · x · (1 − x) / (L · 2fs), where x = Vin/(Vbus/2), subtracting 1 when x exceeds 1. The document integrates nonlinear L(i) for its numerical results.
At 350 V and 100 A, lower-bound inductance gives approximately 20.5 A peak-to-peak channel ripple. At 825 V and full channel power, current is approximately 75.8 A and ripple is 19.3 A: 19.3% of rated 100 A, but 25.5% of actual current. A “channel ripple <20%” limit must specify its denominator.
With a Ts/4 shift between channels but a Ts/2 inductor-ripple period, four channels form only two ripple phases. Assuming equal currents and identical parts, the source calculation reaches approximately 6.4% combined ripple with Ts/4 and ≤1.5% with Ts/8. This is conditional on the modulation; inductance tolerance, sharing error and gate delay require measurement.
If each MPPT channel connects to a separate PV string, their input currents do not sum at one node. Define whether the requirement applies to individual input-capacitor current or bus-side current before using a combined-input-ripple limit.
4. Loss budget: include low-input-voltage operation
DC copper loss follows Pdc = I² · Rdc(T). The document uses 3.24 mΩ at 25 °C, approximately 4.18 mΩ at 100 °C, giving 41.8 W DC copper loss at 100 A. Core loss uses iGSE with typical material data, and AC copper loss uses a one-dimensional Dowell estimate. These are development-stage models.
| Operating point | DC copper (W/ch) | AC copper (W/ch) | Core (W/ch) | Total (W/ch) |
|---|---|---|---|---|
| 350 V / 100 A | 41.8 | 1.0 | 21.5 | 64.3 |
| 625 V / 100 A | 41.8 | 0.3 | 5.6 | 47.6 |
| 825 V / 75.8 A | 24.0 | 0.9 | 25.1 | 50.0 |
| 1000 V / 62.5 A | 16.3 | 0.3 | 8.9 | 25.5 |
| 350 V / 120 A overload | 60.1 | 1.3 | 21.5 | 82.9 |
Lower-bound inductance and 100 °C winding temperature. At normal current, 350 V / 100 A gives the worst total loss, approximately 257 W across four channels. Core loss is higher at 825 V, so that operating point also needs thermal testing.
5. Thermal paths and insulation at 60 °C ambient
A 257 W loss budget and 30 K rise require a total hot-spot-to-ambient resistance of approximately 0.12 K/W or less. The ideal surface area of a 200 × 150 × 100 mm enclosure is approximately 0.13 m². Removing all heat through that surface would require an equivalent heat-transfer coefficient of about 66 W/(m²·K), before internal winding-to-case gradients.
Airflow, effective surface area and the baseplate interface are not yet fixed, so “forced air” alone does not establish compliance. The document proposes a conductive base path to a heatsink or cold plate and control of winding–potting–case, core–base and base–heatsink thermal resistances. Instrument inner windings, cores, terminals and the base.
The development drawing lists winding-to-core tests of 3 kVAC / 60 s with leakage ≤5 mA, insulation resistance ≥100 MΩ at 500 VDC, and Class F or higher insulation. Applicable standards and editions, switching overshoot, overvoltage category, pollution degree, altitude and materials remain project inputs. These tests do not replace a complete insulation design review.
6. Sample validation and RFQ inputs
- Measure each channel's room-temperature and hot L-I curve at least at 0, 76, 100, 110 and 120 A; verify ≥80 µH at 100 A.
- Use four-wire DCR measurements corrected to 25 °C, recording terminals, joints and channel spread.
- Test 350 V, 625 V and 825 V with controlled airflow and base conditions to thermal steady state; verify overload for its specified duration.
- Measure individual and combined currents under actual PWM timing; confirm phase shift, denominator, measurement node and coupling.
- Complete dielectric, insulation-resistance, thermal-cycle, vibration, acoustic-noise and potting-quality checks.
For an RFQ, provide topology, channel count, shared or separate inputs, voltage range, channel current and overload, switching frequency and modulation, inductance at a stated current, coupling, ripple definitions, cooling and mounting conditions, insulation requirements and annual volume.
FAQ
Why review a 147 µH inductor against 80 µH at 100 A?
The 147 µH value is at zero bias. DC bias reduces permeability, so acceptance uses loaded inductance with temperature and material-batch boundaries.
Does four-phase interleaving guarantee combined ripple below 5%?
No. Confirm the ripple period, channel phase shift, input summation, part tolerances and actual measurement node.
Is 257 W a measured loss?
It is the document's four-channel estimate using lower-bound inductance, a 100 °C winding and other stated assumptions. Actual loss and temperature rise require sample tests.
English PDF technical article
PMT-DOC-2026-0927-02 · Rev A/0 · 2026-09-27 · 7 pages
Download English PDF (7 pages)中文文章Related technical resources
20–60 kW three-phase PFC inductor selection
500 A high-current inductor design
Thermal design and temperature-rise testing
Send your project parameters
SHENZHEN PROMAGTECH CO.,LTD.
3F, Bldg 1, No.22 Dongda Rd, Fenghuang St., Guangming District, Shenzhen 518132, China