PV MPPT · Four-in-One Boost Inductor

How to Design a Four-in-One Boost Inductor for a 250 kW PV MPPT

A development-stage review of loaded inductance, three-level interleaved ripple, four-channel losses and baseplate cooling for a 250 kW PV MPPT magnetic assembly.

Design focus: The example calculates 111 µH typical and 97 µH lower-bound inductance at 100 A, with approximately 257 W worst-case loss across four channels. Phase shift, ripple definitions, coupling and the thermal boundary still require confirmation and sample validation.

PMT-DOC-2026-0927-02 · Rev A/0 · 2026-09-27

Download English PDF (7 pages)中文文章
English concept illustration of a 250 kW MPPT four-in-one boost inductor with an aluminum potted enclosure and application examples
Development concept rendering. Terminals, construction and mounting follow the project drawing; performance is established by sample tests under actual operating conditions.

1. Freeze the operating envelope: 250 kW is not constant power over the full input range

The example uses a four-phase interleaved three-level boost, with a 350–1000 VDC input range, 1100 VDC maximum and a 1100 V calculation bus. Switching frequency is 32 kHz. Each channel is limited to 100 Arms and 62.5 kW: current-limited below 625 V and power-limited above. Four inductors share a potted 200 × 150 × 100 mm aluminum enclosure at 60 °C ambient, with a temperature-rise target below 30 K.

InputDocument conditionConfirmation required
Loaded inductance≥80 µH at 100 AAcceptance at load; zero-bias value for incoming inspection
Overload110% / 10 min; 120% / 1 minInductance, loss and temperature at 120 A
RippleChannel <20%; combined <5%Rated or actual-current denominator; summation node
CouplingInput requirement 0.2; design ≤0.05Independent or coupled paths, agreed with the control engineer
DCR and cooling<4 mΩ at 25 °C to be confirmed; forced airFinal DCR limit, airflow and baseplate interface

2. Four independent UU paths and inductance at 100 A

Each channel uses a 60µ FeSi powder UU core, with Ae = 1169 mm² and le approximately 194 mm. Two nine-turn coils are connected in series for 18 turns, using edgewound 2.0 × 10 mm flat copper. The four paths are independent, with a design coupling coefficient ≤0.05; combined-ripple cancellation relies on control phase shift.

Zero-bias model: L0 = N² · µ0 · µi · Ae / le ≈ 147.2 µH. At 100 A, H = N · I / le ≈ 9278 A/m. The document fits DC-bias roll-off to a material curve. The following values are calculated and exclude the temperature dependence of permeability.

CurrentTypical L (µH)Lower-bound L (µH)
0 A147135
76 A125111
100 A11197
110 A10591
120 A9986

The 147 µH zero-bias value cannot replace acceptance at 100 A. For incremental inductance that falls with current, review stored energy using W = ∫ i · L(i) di instead of only substituting the operating-point inductance into ½LI². Measured room-temperature and hot L-I curves take precedence.

3. Separate channel ripple, combined ripple and phase shift

Under the article's three-level modulation assumption, the inductor voltage switches in Vbus/2 steps and ripple frequency is 2fs = 64 kHz. Verify this against the actual PWM timing. The linear approximation is ΔIpp = (Vbus/2) · x · (1 − x) / (L · 2fs), where x = Vin/(Vbus/2), subtracting 1 when x exceeds 1. The document integrates nonlinear L(i) for its numerical results.

At 350 V and 100 A, lower-bound inductance gives approximately 20.5 A peak-to-peak channel ripple. At 825 V and full channel power, current is approximately 75.8 A and ripple is 19.3 A: 19.3% of rated 100 A, but 25.5% of actual current. A “channel ripple <20%” limit must specify its denominator.

With a Ts/4 shift between channels but a Ts/2 inductor-ripple period, four channels form only two ripple phases. Assuming equal currents and identical parts, the source calculation reaches approximately 6.4% combined ripple with Ts/4 and ≤1.5% with Ts/8. This is conditional on the modulation; inductance tolerance, sharing error and gate delay require measurement.

If each MPPT channel connects to a separate PV string, their input currents do not sum at one node. Define whether the requirement applies to individual input-capacitor current or bus-side current before using a combined-input-ripple limit.

4. Loss budget: include low-input-voltage operation

DC copper loss follows Pdc = I² · Rdc(T). The document uses 3.24 mΩ at 25 °C, approximately 4.18 mΩ at 100 °C, giving 41.8 W DC copper loss at 100 A. Core loss uses iGSE with typical material data, and AC copper loss uses a one-dimensional Dowell estimate. These are development-stage models.

Operating pointDC copper (W/ch)AC copper (W/ch)Core (W/ch)Total (W/ch)
350 V / 100 A41.81.021.564.3
625 V / 100 A41.80.35.647.6
825 V / 75.8 A24.00.925.150.0
1000 V / 62.5 A16.30.38.925.5
350 V / 120 A overload60.11.321.582.9

Lower-bound inductance and 100 °C winding temperature. At normal current, 350 V / 100 A gives the worst total loss, approximately 257 W across four channels. Core loss is higher at 825 V, so that operating point also needs thermal testing.

5. Thermal paths and insulation at 60 °C ambient

A 257 W loss budget and 30 K rise require a total hot-spot-to-ambient resistance of approximately 0.12 K/W or less. The ideal surface area of a 200 × 150 × 100 mm enclosure is approximately 0.13 m². Removing all heat through that surface would require an equivalent heat-transfer coefficient of about 66 W/(m²·K), before internal winding-to-case gradients.

Airflow, effective surface area and the baseplate interface are not yet fixed, so “forced air” alone does not establish compliance. The document proposes a conductive base path to a heatsink or cold plate and control of winding–potting–case, core–base and base–heatsink thermal resistances. Instrument inner windings, cores, terminals and the base.

The development drawing lists winding-to-core tests of 3 kVAC / 60 s with leakage ≤5 mA, insulation resistance ≥100 MΩ at 500 VDC, and Class F or higher insulation. Applicable standards and editions, switching overshoot, overvoltage category, pollution degree, altitude and materials remain project inputs. These tests do not replace a complete insulation design review.

6. Sample validation and RFQ inputs

For an RFQ, provide topology, channel count, shared or separate inputs, voltage range, channel current and overload, switching frequency and modulation, inductance at a stated current, coupling, ripple definitions, cooling and mounting conditions, insulation requirements and annual volume.

Data notice: Based on PMT-DOC-2026-0927-02 Rev A/0. Values are development-stage calculations with the limits of fitted L-I, typical material loss, one-dimensional AC copper-loss and lumped thermal models. They are not sample measurements or project-release evidence. Complete equations, plots and the validation matrix are in the English PDF below.

FAQ

Why review a 147 µH inductor against 80 µH at 100 A?

The 147 µH value is at zero bias. DC bias reduces permeability, so acceptance uses loaded inductance with temperature and material-batch boundaries.

Does four-phase interleaving guarantee combined ripple below 5%?

No. Confirm the ripple period, channel phase shift, input summation, part tolerances and actual measurement node.

Is 257 W a measured loss?

It is the document's four-channel estimate using lower-bound inductance, a 100 °C winding and other stated assumptions. Actual loss and temperature rise require sample tests.

English PDF technical article

PMT-DOC-2026-0927-02 · Rev A/0 · 2026-09-27 · 7 pages

Download English PDF (7 pages)中文文章

Related technical resources

20–60 kW three-phase PFC inductor selection

500 A high-current inductor design

Thermal design and temperature-rise testing

Send your project parameters

SHENZHEN PROMAGTECH CO.,LTD.

3F, Bldg 1, No.22 Dongda Rd, Fenghuang St., Guangming District, Shenzhen 518132, China

zyong@promagtech.cn · +86 13267069291 · www.promagtech.com